- Pin refinishing involving the application of flammable finishes shall be done only in a special room meeting the requirements for a Type B inside storage or mixing room (for details see the Fire Prevention Code adopted by section 609 of this title); such room shall not be located below grade nor shall it have communication with any pits, wells, pockets or basements.
- Storage of flammable liquids in such rooms shall not exceed a combined aggregate of 60 gallons in original metal containers, or approved safety containers not exceeding 5 gallons individual capacity. A metal waste can with self-closing cover shall be provided for all waste materials and rags; contents shall be removed daily. Smoking shall be prohibited at all times in refinishing rooms.